General Provisions:
MACT Determinations -
The MACT Floor Finding
Main : 1 : 2 : 3 : 4 : 5 : 6 : 7
The MACT Floor Finding
This section will explain four approaches for determining a MACT floor. If the emissions information is available, the first three methods should be considered before the permitting authority concludes that a MACT floor cannot be determined. The three emissions-based methods include using:
- Existing state and local air toxic control regulations;
- Control efficiency ratings; or
- Emission reduction ratios.
A fourth method, the technology approach, can be used when
insufficient emissions data are available to determine an average emissions limitation.
The first method compares air pollution regulations in
different states. The second method is applicable when the
control technologies under consideration can be assigned an
efficiency rating for HAP emission reductions. This is most
likely to occur with add-on control devices. The third method
can be used for add-on control devices, work practices,
recycling, reuse or pollution prevention strategies. Depending
on the format of available information, a hybrid of the three
approaches may be necessary. The fourth method involves
determining which technology is being used by the best performing
sources in the category and then determining the emissions limit that the technology
is capable of achieving in practice on a continuous basis.
Calculation of the MACT Floor
The Clean Air Act (as amended in 1990) instructs the US EPA to set emission
standards for new sources based on the emissions control achieved
in practice by the best controlled similar source and to set
emission standards for existing sources based on an average emission limitation achieved by the best performing 12 percent of
existing sources or best performing five sources in the source
category or subcategory for categories with fewer than
30 sources.
The word "average" can have several different meanings,
including arithmetic mean, median, and mode. As stated previously, the EPA published a Federal Register notice
describing these methods of determining the average as well as
other common sense considerations at 59 FR 29196 et.seq., June 6,
1994. A copy of this notice is contained in Appendix B of on Guidelines for MACT Determinations under Section 112(j) Requirements[PDF]
The following examples illustrate the average as represented
by the mean, median, and mode.
Example 1
% Reduction |
Comments |
95 |
- Number of sources in the best performing 12% = 7
- Average emission limitation : 644/7 = 92%
- In this case the MACT floor would be 92%
|
95 |
93 |
93 |
92 |
88 |
88 |
Total: 644 |
Under some circumstances the arithmetic mean results in a
number that may not correspond to the application of a specific
control technology. If there is a large discrepancy between the
amount of emission reductions that can be achieved by available
control options, other factors should be considered to determine
the MACT floor. This is illustrated with the following example:
Example 2
An arithmetic mean is computed for the best performing
12 percent of storage tanks. There are 10 sources among the
best performing 12 percent of storage tanks. Two tanks are
controlled at 99 percent, and the remaining 8 tanks are not
controlled. The emissions limitations considered in the
floor calculation are:
% Reduction |
Comments |
99 |
- Number of sources in the best performing 12% = 10
- Average emission limitation = 19.8%
- In this example, no technology corresponds to 19.8% control, and it might be inappropriate to elevate the MACT floor to 99% control.
|
99 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
Total: 198 |
If there is a large discrepancy between the amount of
emission reductions that can be achieved by available control options, the median should be used in lieu of the arithmetic mean
to determine the average emission limitation equal to the MACT
floor. A median is the value that falls in the middle of a set
of numbers when those numbers are arranged in an increasing order
of magnitude; in other words, there will be an equal number of
values above and below the median. If the middle falls between
two values, the median is equal to the arithmetic mean of those
two numbers. This situation will occur when there is an even
number of values in the set of numbers. In this example, the
median would be 0-percent reduction, and this could be selected
as the MACT floor.
However, if there is a large discrepancy between the control technologies used to establish a median such that no technology
could realistically obtain a reduction close to the median, the
mode should be used to calculate the MACT floor. A mode is the
most frequent occurrence among a set of data. In Example 1, there are two modes, 95-percent and 88-percent emission
reductions. In Example 2, the mode would be equal to 0-percent
emission reduction. When there is more than one mode in the data
set, the MACT floor should be based on the least degree of
emission control. However, the existence of more than one mode
may be an indicator that the MACT should be established at a
level of control more stringent than the MACT floor.
The mode may also be used as a method to compute an average
emission limitation if the emissions data for a source category or subcategory are not numerically based. This situation could
occur if sources were regulated by several different equipment or
work practice standards. Unless a specific level of emission
reduction can be associated with each different standard or
unless the standards can be ranked in some order of increasing
level of control, an arithmetic mean and median cannot be
calculated. A mode could be used if one of the control options
is used more frequently by the best performing 12 percent of
existing sources. This is illustrated in the Example 3 below:
Example 3
- There are 44 tanks in the source category or subcategory.
- Five sources are among the best performing 12 percent of
existing sources. These five tanks are subject to the
following regulations in the source category or subcategory:
3 of the 5 must be covered and vented to a carbon canister;
2 of the 5 must use a fixed roof.
The mode would be to cover and vent the tank to a carbon
canister.
Trouble with PDF files? Download the latest version of Acrobat
Reader.
Return
to Top |